Circuit Breaker Trip Curve Selection Guide and Ordering Tables

Warning!
This information should only be used as a selection guide. The use of a Circuit Breaker in an application with a certain Trip-Characteristic always requires prototype testing! It is the responsibility of the circuit design engineer to select the appropriate Circuit Breaker for his specific application.

Part One

Applications

 

Trip-Characteristics*

Characteristic Trip Boundaries
Thermal Trip Magnetic Trip
Must not Trip>1hr Must Trip <1hr Must not Trip >100ms Must Trip at 100ms
 
 Lighting Wiring Protection  Business Equipment  Appliances  Control Circuits  Transformers  Power Supplies
B-Characteristic **
 1.13xRC  1.45xRC  3xRC  5xRC

+

+

+

+

+

.
C-Characteristic **
 1.13xRC  1.45xRC  5xRC  10xRC

+

+

+

+

+

.
D-Characteristic **
 1.13xRC  1.45xRC  10xRC  16xRC
. . . . .

+

+

E-Characteristic **
 1.05xRC  1.35xRC  14xRC  18xRC
             
G-Characteristic **
 1.05xRC  1.35xRC  8xRC 10xRC

+

+

. .

+

+

.
Z-Characteristic **
 1.05xRC  1.35xRC  2xRC  3xRC
. . . . . . .
*The values of each characteristic are shown vertically beneath it's corresponding heading. ** Click for PDF file.

Time Versus Current Trip Curve

IT'S HERE !
Updated
Short Form with Ordering Tables

Altech short form with ordering information:
Click any of the following to download as a PDF* file viewable in your browser or to print.

Part Two

Applications

 

Trip-Characteristics*

Characteristic Trip Boundaries
Thermal Trip Magnetic Trip
Must not Trip>1hr Must Trip <1hr Must not Trip >100ms Must Trip at 100ms
 

Motors
 
Heaters General Low
Inrush

High
Inrush

High
Efficiency
General Electronics Solenoid Semi- conductors Components/ devices with low surge- current and short circuit withstand capabilities Reactive Load
B-Characteristic **
 1.13xRC  1.45xRC  3xRC  5xRC
. .    

+

. . . .
C-Characteristic **
 1.13xRC  1.45xRC  5xRC  10xRC
. .

+

    . . . . .
D-Characteristic **
 1.13xRC  1.45xRC  10xRC  16xRC

+

.

+

. . . .

+

E-Characteristic **
 1.05xRC  1.35xRC  14xRC  18xRC
       

+

         
G-Characteristic **
 1.05xRC  1.35xRC  8xRC 10xRC
.

+

+

   

+

. . .
Z-Characteristic **
 1.05xRC  1.35xRC  2xRC  3xRC
. .    

+

+

+

.
*The values of each characteristic are shown vertically beneath it's corresponding heading. ** Click for PDF file.

*Portable Document Format (PDF) file, for viewing, printing, navigating and searching on any platform-Macintosh®, Windows®, or UNIX® -with Acrobat Reader with SEARCH. You can even use Acrobat Reader with SEARCH to view PDF files within the leading Web browsers.

CLICK HERE FOR SIMPLE ACROBAT USEAGE INSTRUCTIONS

Terminal Blocks Circuit Breakers Foot Switches Fuses
Sensors Safety Relays Enclosures Strain Reliefs

For more information contact us at:


35 Royal Road
Flemington, NJ 08822-6000
Tel. (908) 806-9400
Fax (908) 806-9490
Map to Altech
Click here to fill out our catalog request form.

Copyright 1997 Altech Corp. Send Comments to altech@altechcorp.com.
This file was last modified on 06/02/2000.